Feature

☆  8 x Loops (242) capacity (1936) addressable points
☆ Maximum 10 Loops Standalone
☆ Modular constructed for future expansion
☆ 40 x15 lines LCD Display
☆  Up to 999 programmable zones and 140 zones’ indication
☆  Day and Night Mode
☆  Enable and Disable function
☆  PAS and Acknowledge Function
☆  Dirty Detector Reporting
☆  Duplicate Address Checking
☆  Device Mismatch Checking
☆  Walk Test Function with optional silent mode
☆  Programmable from PC or Panel
☆  History record – 999 fire incident and 999 general events capacity in non-volatile memory
☆  Advanced user friendly programming software including ‘Fuzzy Logic’
☆  Networkable with GST Intelligent Fire panels up to 64 nodes
☆  Optional GST-GMC graphic station
☆  Optional RS 485 mimic and repeater up to 64
☆  Built in Fire Alarm, FPE, Fault and Alarm Router output
☆  Panel Printer included
☆  Built in Battery Charger
☆  Optional protection of re-programming
☆  Approved by LPCB
Technical Specifications

☆ Standard: EN54 Part 2/4
☆ Approvals: LPCB, CE
☆ Main Input Voltage: 220/230VAC (± 10%) 50/60 Hz
☆ Input Current Rating: 1.0A
☆ System Operating Voltage: 24 VDC Nominal
☆ Loop Capacity: Loop 1-10: 242- Address per loop
☆ Zone Capacity: 999 Zones programmable
☆ Outputs (3):
Fire Routing: 200mA /24Vdc/4.7KΩ EOLR
F.P.E. Output: 500mA /24Vdc/4.7KΩ EOLR
Sounder Circuit Output: 1A /24Vdc/4.7KΩ EOLR
☆ Dimension: (HWD) 850 x 484 x 191 mm